MP-99 Microprocessor

At the heart of ULTRAMATIX Precision Air conditioners is MP-99 Microprocessor System offering total control of Air Flow, Cooling, Heating, Humidification & Dehumidification functions. MP-99 ensures that desired Temp. & RH conditions are achieved in room quickly & are subsequently maintained on 24 hrs x 365 days basis.

MP-99 Microprocessor Features

image143

Simultaneous PID Control of Critical Parameters

MP-99  has built in proprietary software for PID Control of   Cooling/Heating/Humidification/ Dehumidification & Comprressor High/Low   pressures simultaneously.

Software Features

  • Real Time Clock & Calendar.
  • Password Protection .
  • 39 Different Alarms.
  • 53 Status Indications.
  • Last 10 Alarms with Date & Time of occurrence.
  • SET facility for Temp/ RH setpoints .
  • Graphical Symbols for critical parts ON/OFF status to know unit status at-a -glance.
  • RS232C /RS 485 Outputs for Communication to external devices
  • 32 Character Alfanumaric LCD  Display.
  • 8 Keys Data Entry  .
  • Self Diagnosis with  Failure Guided Search.
  • Battery Backed RAM for 10 Years data storage & retention.
  • Analog/Digital Inputs & Outputs.

32 Character Alfa-numeric LCD Display

MP-99  Microprocessor  is designed with 32character Alfa numeric LCD  display which can display easily readable  Temp/RH values, Alarms  & Status Messages. 

8 key easy to operate keyboard

MP-99 has a 9 key keyboard consisting of dedicated keys for SET / RESET / ALARM  SILENCE  /INFORMATION for ease of operator  use .

Guided Failure Search

MP-99 offers guided failure search using the INFORMATION key for various possible failures of the Unit  and its sensors for immediate attention.

Serial Output for remote Monitoring & BMS.

MP-99 offers serial output using RS 232 C /RS 485  ports which can be used to monitor & Control the Precision AC Units remotely using  REMOTE MONITORING SYSTEMS or Building Management Systems .

MP-99 Microprocessor Features

MP-99 Construction

Graphical Symbols for at - a -glance unit status

MP-99 Construction

image144

MP-99 is designed as a set of individual PCBs for :

  • Temp/RH sesor. 
  • Display & Keyboard.
  • A/D  & D/A Converter PCBs.
  • Relay Output PCB.
  • Microprocessor Mother PCB

Password Control

Graphical Symbols for at - a -glance unit status

MP-99 Construction

image145

MP-99  is PASSWORD protected for avoiding use & changes by an unauthorised person. 

Graphical Symbols for at - a -glance unit status

Graphical Symbols for at - a -glance unit status

SET key to set Temp/RH set points & Hi/Low Limits

image146

MP-99  Display shows Graphical Symbols for AUto/Manual mode of working of  Compressors, Fan, Humidifier, Heaters , Dehumidifier & Water Inlet/Outlet Valves to understand unit status  at -a -glance.

SET key to set Temp/RH set points & Hi/Low Limits

SET key to set Temp/RH set points & Hi/Low Limits

SET key to set Temp/RH set points & Hi/Low Limits

image147

SET key allows programming of  53 nos of factory set set-points of the unit  :

  • Temp/RH set Points.
  • Clock & Calender.
  • Hi/Low Temp. & RH  Limits.
  • Hi/Low AC Line Voltage Set Points.
  • Comp 1/2 start Delays 

MANUAL Mode of Operation

SET key to set Temp/RH set points & Hi/Low Limits

MANUAL Mode of Operation

image148

MP-99 can be put in MANUAL  mode with this key to run following components manually  :

  • Compressors 1 & 2
  • Heaters 1 & 2.
  • Humidifier.

Remote Monitoring System

SET key to set Temp/RH set points & Hi/Low Limits

MANUAL Mode of Operation

image149

Mp-99  can be connected to the Remote Monitoring System  or a Building Management System through RS 232 C Serial data output of MP-99

MP-99 Status Indications

On/Off & Manual On/Off Status of Critical Parts

Display of Set Points & HP/Voltage/Current Values

Display of Set Points & HP/Voltage/Current Values

image150

MP-99 STATUS displays ON/OFF or MANUAL ON /  OFF status indications of :

  • Compressors- 1 & 2 
  • Heaters 1 & 2  .
  •  Humidifier .
  • Cooling & Heating Valves.
  •  Condenser Fans 1 & 2 , 

Display of Set Points & HP/Voltage/Current Values

Display of Set Points & HP/Voltage/Current Values

Display of Set Points & HP/Voltage/Current Values

image151

MP-99 STATUS displays : 

  • Temp. & RH Set  Points, 
  • Humidifier Current, 
  • Date & TIme, 
  • Comp. 1 & 2 High Pressure in  kpA, 
  • AC Line Voltage & Current, 
  • Outlet  & Ambient Temperature. 

Hours in use & No. of Starts Counters

Display of Set Points & HP/Voltage/Current Values

Hours in use & No. of Starts Counters

image152

MP-99 STATUS displays Hours of use Counter for  :

  • Compressor 1 & 2.
  • Heaters 1 & 2
  • Humidifier & Dehumidifier.
  • Fan.

No. of Starts Counter for Compressor 1 & 2 .

Last 10 Alarms with Date & Time

Last 10 Alarms with Date & Time

Hours in use & No. of Starts Counters

image153

MP-99 STATUS Indications display last 10 alarms logged in the  Precision AC for ease of mtce & daily chedcks stamped with Date & Time of occurance. 

Maintenance Status

Last 10 Alarms with Date & Time

Communication & Chrono

image154

MP-99  STATUS shows  MAINTENANCE level status of  parts such as  Compressors, Heaters etc on level of  1 to 5 depending on their hours of the  use to take maintenance actions.

Communication & Chrono

Last 10 Alarms with Date & Time

Communication & Chrono

image155

MP-99  STATUS allows setting of communication baud rate for  devices such as Laptops, Tabs etc.  


CHRONO mode can be set in STATUS  for machine On/OFF at a predetermined date & time & auto changeover of  Hot Standby units.

MP-99 Alarms

Compressor 1 & 2 Alarms

Deviation from Set Points Alarms

Compressor 1 & 2 Alarms

image156

MP-99 offers following alarms for Comp1 & 2 :

  •  Hight Pressure C 1 & C2.
  • Low Pressure C 1 & C2.
  • Overload C1 & C2.
  • Condenser Fan Fail 1 & 2 .

Humidifier Alarms

Deviation from Set Points Alarms

Compressor 1 & 2 Alarms

image157

MP-99 Offers following Alarms for Humidifier 

  • Humidifier Cylinder Exhausted.
  • Hi & No Current Humidifier.
  • Fill Time Too Long /No Capacity
  • In 14 Minutes no Humidification

Deviation from Set Points Alarms

Deviation from Set Points Alarms

Deviation from Set Points Alarms

image158

MP-99 offers alarms for :

  • Hi /Low Room Tempeature.
  • Hi/Low Room Humidity.
  • Hi Pressure C1 & C2 .
  • High/Low AC Mains Voltage

Failure Alarms

Failure Alarms

Deviation from Set Points Alarms

image159

MP-99 offers maintenance alarms as under :

  • Logic Fail.
  • Tempeature Sensor Fail.
  • Humidity Sensor Fail.
  • External Power Switch  OFF
  • Maintenance of Devices Due 

Safety Alarms

Failure Alarms

Safety Alarms

image160

MP-99 offers following Safety Alarms :

  • Smoke/Fire  
  • Water Under Floor.
  • Dirty Filters.
  • Air Flow Loss.
  • Supply Fan Fail.
  • Heater Safety Switch tripped.

MP-2060 GUI

Failure Alarms

Safety Alarms

image161

MP-99 can be optionally connected to MP-2060 GUI-Graphic User Interface to see the  Temp/RH trends in graphical forms over the time elapsed.